• 1
  • 2
Product Range
 
Air Cooled Chiller
Air Cooled Screw Chiller Series
Views:3495   Updated:2014/7/18 0:07:58


FEATURES

STRUCTURE

The master module can work independently or together with up to 11 slave modules, cooling capacity from 150 to 1180kW.

HERMETIC COMPRESSOR

3-phase Semi-hermetic screw compressor, with built-in thermal overload cut-out , mounted on rubber vibration dampers.

AXIAL FAN

External rotor type axial fans, equipped with three phase direct drive motors, low noise 8 poles, protection level IP55,F class provided with a protective outlet grille.

EVAPORATOR

Evaporator built with high efficiency tube in tube type or shell and tube heat exchanger, factory insulated with flexible close cell material.

CONDENSER

Condenser built with seamless internal screw thread copper tubes mechanically expanded into blue wave hydrophilic aluminum fins.

HEAT RECOVERY

The user needs to be able to realize the full 0-100% condensing heat recovery and recycling too cool heating

HYDRAULIC CIRCUIT

Hydraulic circuit built with galvanized pipe, complete with water discharge connection for heat exchanger and flange type hydraulic connectors in two directions easy for connections from both sides of the units.

ELECTRIC PANEL

Electric panel consist of: Compressor contactor, fan motor contactor, compressor protection breaker, fan protection breaker, phase sequence relay and microprocessor with function display (display only for master/packaged unit)

Automatic operation dramatically reducing maintenance cost thanks to reliable microprocessor system.

TECHNICAL DATA(R134a)

Model

Unit

150

180

250

320

380

Cooling capacity *

kW

156

180

250

320

380

Heating capacity *

kW

180

198

276

353

416

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

Type

 

R134a

Quantity

kg

38

48

64

82

100

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

1

1

1

1

1

Cooling power input *

kW

49.3

54.2

77.4

96.7

114

Cooling current *

A

87.8

95.2

134

166

199

Heating power input *

kW

48.4

53.2

76

95

112

Heating current *

A

86.5

93.7

132

164

196

Energy adjustment steps

step

4

3

4

3

3

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

26.7

31

42.8

54.8

65

Water side pressure drop

kPa

41

41

42

42

42

Water pipe

 DN

100

100

100

125

125

Axial Fan

 

Fan motor number

Nr.

4

4

6

6

8

Power input

kW

4*2.2

4*2.2

6*2.2

6*2.2

8*2.2

Current input

A

4*5.6

4*5.6

6*5.6

6*5.6

8*5.6

Air flow

m3/h

68000

96000

144000

144000

196000

Dimensions

 

L

mm

2500

2500

3300

3590

4680

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

73

73

75

75

78

Net weight

kg

2050

2350

2750

3150

3650


Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃

TECHNICAL DATA(R134a)


Model

Unit

430

500

570

640

700

Cooling capacity *

kW

428

497.6

568

637.8

700

Heating capacity *

kW

474

550

630

706

772

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

 

Type

 

R134a

Quantity

kg

65*2

77*2

82*2

98*2

105*2

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

2

2

2

2

2

Cooling power input *

kW

131.6

154.8

174.1

193.4

210.7

Cooling current *

A

229.2

268

300

332

365

Heating power input *

kW

129.2

152

171

190

207

Heating current *

A

225.7

264

296

328

360

Energy adjustment steps

step

4

4

3

3

3

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

74

85.6

97.4

109.7

120

Water side pressure drop

kPa

42

43

43

44

45

Water pipe

 DN

125

125

125

150

150

Axial Fan

 

Fan motor number

Nr.

10

12

12

12

14

Power input

kW

10*2.2

12*2.2

12*2.2

12*2.2

14*2.2

Current input

A

10*5.6

12*5.6

12*5.6

12*5.6

14*5.6

Air flow

m3/h

240000

288000

288000

288000

333600

Dimensions

 

L

mm

5800

6790

6790

7190

8280

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

80

81

81

81

82

Net weight

kg

4800

5250

5600

6150

6900


Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃

TECHNICAL DATA(R134a)


Model

Unit

760

870

930

1000

1180

Cooling capacity *

kW

758

868

923.8

992.8

1172

Heating capacity *

kW

827

953

1014

1086

1264

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

 

Type

 

R134a

Quantity

kg

115*2

75*3

80*3

85*3

100*3

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

2

3

3

3

3

Cooling power input *

kW

228

268.8

286.4

309.6

348.2

Cooling current *

A

398

467

497.2

536

600.4

Heating power input *

kW

224

264

281.2

304

342

Heating current *

A

392

460

489.7

528

591.2

Energy adjustment steps

step

3

3

3

3

3

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

130

149

159

170.8

201.6

Water side pressure drop

kPa

45

45

45

45

45

Water pipe

 DN

150

150

150

150

200

Axial Fan

 

Fan motor number

Nr.

16

18

18

18

20

Power input

kW

16*2.2

18*2.2

18*2.2

18*2.2

20*2.2

Current input

A

16*5.6

18*5.6

18*5.6

18*5.6

20*5.6

Air flow

m3/h

384000

432000

432000

432000

576000

Dimensions

 

L

mm

9370

10290

10580

10980

11780

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

83

83

83

83

83

Net weight

kg

7600

8900

9650

10000

11000

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃

TECHNICAL DATA(R407c)


Model

Unit

150

180

250

320

380

Cooling capacity *

kW

150

180

250

320

380

Heating capacity *

kW

170

202

276

357

425

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

 

Type

 

R134a

Quantity

kg

38

48

64

82

100

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

1

1

1

1

1

Cooling power input *

kW

50

60.4

81

103

126

Cooling current *

A

85

104

137.6

174

213.3

Heating power input *

kW

48.7

58.8

79

100.5

123

Heating current *

A

83

101.4

134

170

208

Energy adjustment steps

step

4

4

4

4

4

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

25.7

31

42.8

54.9

65

Water side pressure drop

kPa

41

41

42

42

42

Water pipe

 DN

100

100

100

125

125

Axial Fan

 

Fan motor number

Nr.

4

4

6

6

8

Power input

kW

4*2.2

4*2.2

6*2.2

6*2.2

8*2.2

Current input

A

4*5.6

4*5.6

6*5.6

6*5.6

8*5.6

Air flow

m3/h

68000

96000

144000

144000

196000

Dimensions

 

L

mm

2500

2500

3300

3590

4680

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

73

73

75

75

78

Net weight

kg

2050

2350

2750

3150

3650

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃

Model

Unit

430

500

570

640

700

Cooling capacity *

kW

428

498

563

632

699

Heating capacity *

kW

476

550

627

710

780

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

 

Type

 

R134a

Quantity

kg

65*2

77*2

82*2

98*2

105*2

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

2

2

2

2

2

Cooling power input *

kW

141.4

162

184

206

229

Cooling current *

A

241.6

275.2

311.6

348

387.3

Heating power input *

kW

137.8

158

179.5

201

223.5

Heating current *

A

235.4

268

304

340

378

Energy adjustment steps

step

4

4

4

4

4

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

74

85.6

96.5

108.7

120

Water side pressure drop

kPa

42

43

43

44

45

Water pipe

 DN

125

125

125

150

150

Axial Fan

 

 

Fan motor number

Nr.

10

12

12

12

14

Power input

kW

10*2.2

12*2.2

12*2.2

12*2.2

14*2.2

Current input

A

10*5.6

12*5.6

12*5.6

12*5.6

14*5.6

Air flow

m3/h

240000

288000

288000

288000

333600

Dimensions

 

 

L

mm

5800

6790

6790

7190

8280

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

80

81

81

81

82

Net weight

kg

4800

5250

5600

6150

6900

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃

TECHNICAL DATAR407c                                                                  

Model

Unit

760

870

930

1000

1180

Cooling capacity *

kW

760

865

925.6

992

1164

Heating capacity *

kW

850

967

1012

1088

1250

Power supply

V/PH/Hz

380/3/50/60

Refrigerant

 

 

Type

 

R134a

Quantity

kg

115*2

75*3

80*3

85*3

100*3

Control method

 

Thermal expansion valve

Compressor

 

Semi-hermetic screw compressor

Qty/refrigerant circuit

Nr.

2

3

3

3

3

Cooling power input *

kW

252

288

303.7

324.4

368.6

Cooling current *

A

426.6

488.2

516.8

550.4

623.2

Heating power input *

kW

246

281

295.8

316

359

Heating current *

A

416

476

503.7

536.4

607.2

Energy adjustment steps

step

4

4

4

4

3

Condenser

type

Fin heat exchanger

Evaporator 

type

Shell and tube /tube  and tube heat exchanger

Water flow rate 

m3/h

130.7

148.8

159

170.6

200

Water side pressure drop

kPa

45

45

45

45

45

Water pipe

 DN

150

150

150

150

200

Axial Fan

 

 

Fan motor number

Nr.

16

18

18

18

20

Power input

kW

16*2.2

18*2.2

18*2.2

18*2.2

20*2.2

Current input

A

16*5.6

18*5.6

18*5.6

18*5.6

20*5.6

Air flow

m3/h

384000

432000

432000

432000

576000

Dimensions

 

 

L

mm

9370

10290

10580

10980

11780

W

mm

2160

2160

2160

2160

2160

H

mm

2450

2450

2450

2450

2450

Sound pressure level **

dB(A)

83

83

83

83

83

Net weight

kg

7600

8900

9650

10000

11000

Performance values refer to the following conditions:

*Cooling capacity is measured under the condition : Ambient temperature DB 35℃/WB 24℃ ,user side water inlet/outlet temperature 12℃/ 7℃   

*Heating capacity is measured under the condition : Ambient temperature DB 7℃/WB 6℃ ,user side water inlet/outlet temperature 40℃ /45℃


<<<<<< Previous:none              Next:Air Cooled Modular Chiller Series >>>>>>